DCImanager 6
en En
es Es

Configuring a UPS

To manage uninterruptible power supplies (UPS), enter Equipment → UPS.

The UPS table displays the information obtained by polling the devices:

  • charge, min — remaining operating time in the autonomous mode;
  • load, %;
  • output power, kW;
  • input power, kW.
Section interface
Section interface

DCImanager 6 polls the UPS every five minutes. To poll manually, select the device →  menu → Poll.

You can change the UPS settings in the device card. To open the UPS card, click on the device name in the table or enter the menu → Settings.

To delete a UPS, enter the menu → Delete UPS → enter the device ID → Delete.

Connecting equipment

To connect various devices to UPS:

  1. Go to Equipment → UPS → click on the UPS name → Outgoing connections.
  2. Select the device type:
    1. Server;
    2. Switch;
    3. Chassis:
    4. PDU;
    5. UPS;
  3. Select the device location:
    1. In the UPS rack;
    2. In any rack.
  4. Select the device to connect to the switch and click Save.

Connecting to a power supply

To connect UPS to a power supply:

  1. Go to Equipment → UPS → click on the UPS name → Incoming connections.
  2. Click on Connect equipment → Connect to power supply.
  3. Select the device type in the Connection type field:
    1. To an UPS;
    2. To a PDU;
      If there is no suitable equipment in the location, the To an UPS and To a PDU buttons will not be displayed. The Add PDU and Add UPS buttons will appear instead.
  4. Select the device location:
    1. In the UPS rack;
    2. In any rack.
  5. Select the device to connect to the switch and click Save.

UPS without handler

If your UPS model does not have a built-in handler, you can add such a UPS to the platform in "Without handler" mode. To do this, when creating or editing a UPS, select Without handler in the Handler field.

You can write a custom UPS handler. For more information, see the article Creating a UPS handler.

A UPS without handler will operate with limitations:

  • periodic polling of the UPS is not performed;
  • statistics are not collected for the UPS.
If the server is not connected to BMC and is powered only by a UPS without a handler, operations related to power management, including OS installation and reinstallation, will be unavailable for it.

UPS history

The platform keeps a history of UPS operations. For example:

  • adding to the platform;
  • installing in a rack;
  • changing the height or installation type;
  • changing the status as part of warehouse inventory;
  • adding, editing, and deleting notes.

To view the history, go to the Equipment → UPS → click the required device → History.